RENOVA R32 DC Inverter Series

Compare the four RV models

All four share one platform: R32, a Mitsubishi DC inverter compressor, 55 °C maximum water temperature, heating down to −20 °C outdoor, a 7-inch multilingual touchscreen, Wi-Fi and SG Ready. They differ in capacity, electrical supply, hydraulics and size.

Technical data by model. Scroll sideways on small screens.
ModelRV-13-DC-R32RV-19-DC-R32RV-21-DC-R32RV-25-DC-R32
Model class13 kW class19 kW class21 kW class25 kW class
Heating capacity range4 – 13.8 kW4 – 18 kW6 – 22 kW8 – 25 kW
Heating capacity, A7/W3512.2 kW16.1 kW20.0 kW23.0 kW
Power input, heating A7/W352.54 kW3.68 kW4.54 kW5.10 kW
COP, A7/W354.804.374.414.51
Cooling capacity, nominal11.1 kW13.3 kW16.4 kW20.1 kW
Power input, cooling, nominal3.14 kW3.83 kW4.81 kW5.48 kW
Power supply230 V / 50 Hz230 V / 50 Hz230 V / 50 Hz—
Maximum power input4.00 kW5.00 kW6.15 kW8.00 kW
Maximum current18 A23 A28 A36 A
Recommended breaker20 A25 A32 A40 A
Indicative supply cable2.5 mm²4 mm²4 mm²6 mm²
Water connectionDN25DN32DN32DN32
Nominal water flow2.1 m³/h2.8 m³/h3.4 m³/h4.0 m³/h
Minimum water flow27 L/min35 L/min45 L/min45 L/min
Minimum system water volume50 L70 L90 L90 L
Dimensions (W × D × H)1115 × 425 × 960 mm1115 × 425 × 1280 mm1115 × 425 × 1280 mm1115 × 425 × 1440 mm
Net weight125 kg140 kg150 kg160 kg
RefrigerantR32R32R32R32
CompressorMitsubishi DC inverterMitsubishi DC inverterMitsubishi DC inverterMitsubishi DC inverter
Maximum water temperature55 °C55 °C55 °C55 °C
Heating operation down to−20 °C outdoor−20 °C outdoor−20 °C outdoor−20 °C outdoor
Controller7-inch touchscreen, multilingual7-inch touchscreen, multilingual7-inch touchscreen, multilingual7-inch touchscreen, multilingual
ConnectivityWi-Fi · SG ReadyWi-Fi · SG ReadyWi-Fi · SG ReadyWi-Fi · SG Ready
SG ReadyYesYesYesYes
Wi-FiYesYesYesYes
Automatic defrostYesYesYesYes
Smart Home ReadyYesYesYesYes

Heating capacity and COP at A7/W35: outdoor air 7 °C, water outlet 35 °C. Both fall as the outdoor temperature drops or the water temperature rises. Cooling figures are the manufacturer's nominal ratings. Nominal water flow corresponds to the rated heating output at a 5 K flow/return difference. A dash means the value is being confirmed for the current configuration: ask our engineers for RV-25-DC-R32 supply data. The model class is the commercial size designation; always select on the heating capacity at your design outdoor and water temperatures.

Talk to an engineer about your project

Send the building details, location and the emitters you plan to use. We come back with a model proposal and a quotation.

WhatsApp